16 Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March
2. Stringbox with DC Fuse Holders and no DC Switch
The stringbox can be equipped with DC fuse holders and plug-in connectors or cable glands
and a blanking plug instead of the DC switch. A DC switch must be installed separately by
authorized personnel in compliance with the relevant national electrical regulations.
Figure 2.3.8: Optional DC connectors and no DC
switch
P1, P2, P3: Positive connectors
N1, N2, N3: Negative connectors
BP: Blanking Plug
Figure 2.3.9: Stringbox with DC fuse holders and
blanking plug
*N4: Grounding terminal and terminal for
the grounding strap
*P4: Ungrounded terminal
Negative grounded PV String
• Connect the grounding strap between *N4 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).
Positive grounded PV String
• Connect the positive conductors from the positive connectors to the terminal block labeled
Grounded, and the negative conductors to the terminal block labeled Ungrounded.
• Switch the conductors connected to *N4 and *P4.
• Connect the grounding strap between *N4 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).