22 Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March
2.3.5.1. Connection Procedures
Figure 2.3.16: Customer connection area with network
terminals
1. CAN bus terminal
2. Ethernet connector
3. Network cable gland
NOTICE
If multiple inverters are connected together, all inverters must be connected to the CAN bus
before Start Up to benefit from single installation setup.
Ethernet: Use CAT5 or better, with size 0.21 mm
2
/24 AWG, with a maximum length of
100 m.
CAN: Use a cable size 0.13 mm
2
/ 26 AWG, with a maximum length of 100 m.
Unscrew the network cable gland, and take out the grommet.
Three-way cable gland insert:
Figure 2.3.17: Insertion of the network cables in the cable gland
1. Conductors with connector: cut through the grommet with a width of about 1mm. With no
connector: no cutting is necessary
2. Remove the plug from inside the grommet.
3. Assemble the cable in the gap. Repeat step 1 – 3 if more cables.
4. Guide the assembly into the cable gland.
Connect the cables to the terminals in the connection area as follows:
Ethernet CAN
Plug the Ethernet cable directly into the RJ45
socket.
The conductors must be connected to the
same labeled terminals at both ends, i.e. H
connected to H, L to L etc.
Recommended tightening torque is 0.2 Nm /
0.15ft-lbf.
5. Tighten the cable gland firmly.